1.国网电力科学研究院有限公司,江苏省南京市 211106;2.国电南瑞科技股份有限公司,江苏省南京市 211106;3.东南大学电气工程学院,江苏省南京市 210096
针对高比例分布式电源接入下薄弱配电网馈线末端电压越限问题,从变电站端角度提出了计及自动电压控制(AVC)限值调整的配电网调压策略。首先,对配电网中主要可调设备和九区图控制策略进行线性化建模处理;然后,采用增强Epsilon约束法求解计及AVC限值调整的配电网多目标优化问题的Pareto前沿;最后,利用IEEE 33节点标准算例和中国浙江省某实际多馈线配电系统对所提方法进行验证。结果表明,所提方法可以降低可调设备日动作次数,提高设备使用寿命,并有效改善高比例光伏接入下配电网电压波动问题。
国家重点研发计划资助项目(2021YFB2401303)。
1.State Grid Electric Power Research Institute Co., Ltd., Nanjing 211106, China;2.NARI Technology Co., Ltd., Nanjing 211106, China;3.School of Electrical Engineering, Southeast University, Nanjing 210096, China
In order to solve the problem of voltage overlimit at the feeder end of weak distribution network with high proportion of distributed generator, the voltage regulation strategy for distribution network considering automatic voltage control (AVC) limit adjustment is proposed from the substation perspective. Firstly, linearization modeling is carried out for the main adjustable equipment and the nine-zone diagram control strategy in the distribution network. Then, the Pareto front of the distribution network multi-objective optimization problem with AVC limit adjustment is solved by the enhanced Epsilon-constrained method. Finally, the proposed method is validated by an IEEE 33-bus standard case and a practical multi-feeder distribution system in Zhejiang Province, China. The results show that the proposed method can reduce the daily operation times of the adjustable equipment, increase the service life of the equipment, and effectively improve the voltage fluctuation of the distribution network with high proportion of photovoltaics.
[1] | 孙华鹏,丁孝华,吴志,等.计及自动电压控制系统限值优化调整的配电网调压策略[J/OL].电力系统自动化,http://doi. org/10.7500/AEPS20230915002. SUN Huapeng, DING Xiaohua, WU Zhi, et al. Voltage Regulation Strategy for Distribution Network Considering Optimal Adjustment of Automatic Voltage Control System Limits[J/OL]. Automation of Electric Power Systems, http://doi. org/10.7500/AEPS20230915002. |